Universal Changeover Switches |
|
| |
LW26 |
|
| |
.jpg) |
|
| |
LW26 series rotary switches represent the most advanced rotary switches by Andeli group Electrical Appliance Factory. We currently have six models, current rating up to 160A, suitable for wide variety of applications. LW26 series rotary switches are suitable for: on-off of an electrical circuit, change-over of electrical circuits, motor switch, instrument switch, and main switch. |
|
| |
Model |
LW26-20 |
LW26-25 |
LW26-32 |
Rated insulation voltage Ui |
690V |
690V |
690V |
Rated thermal current Ith |
20A |
25A |
32A |
Rated working voltage Ue(V) |
120 |
240 |
440 |
120 |
240 |
440 |
120 |
240 |
440 |
Rated working
current Ie |
AC-21A
AC-22A |
- |
20 |
20 |
- |
25 |
25 |
- |
32 |
32 |
AC-23A |
15 |
15 |
22 |
22 |
30 |
30 |
AC-2 |
15 |
15 |
22 |
22 |
30 |
30 |
AC-3 |
11 |
11 |
15 |
15 |
22 |
22 |
AC-4 |
3.5 |
3.5 |
6.5 |
6.5 |
11 |
11 |
AC-15 |
5 |
4 |
8 |
5 |
14 |
6 |
DC-13 |
5 |
1 |
- |
9 |
1.5 |
- |
25 |
11 |
- |
Power P (KW) |
AC-23A |
- |
3.7/2.5 |
7.5/3.7 |
- |
5.5/3 |
11/5.5 |
- |
7.5/4 |
15/10 |
AC-2 |
4 |
7.5 |
5.5 |
11 |
7.5 |
18.5 |
AC-3 |
3/2.2 |
5.5/3 |
4/3 |
7.5/.7 |
5.5/4 |
11/6 |
AC-4 |
0.55/0.75 |
1.5/1.5 |
1.5/1.5 |
3/2.2 |
2.7/1.5 |
5.5/2.4 |
|
|
| |
.jpg) |
|
| |
Model |
LW26-63 |
LW26-125 |
LW26-160 |
Rated insulation voltage Ui |
690V |
690V |
690V |
Rated thermal current Ith |
63A |
125A |
160A |
Rated working voltage Ue(V) |
240 |
440 |
240 |
440 |
240 |
440 |
Rated working
current Ie |
AC-21A
AC-22A |
63 |
63 |
100 |
100 |
150 |
150 |
AC-23A |
57 |
57 |
90 |
90 |
135 |
135 |
AC-2 |
57 |
57 |
90 |
90 |
135 |
135 |
AC-3 |
36 |
36 |
75 |
75 |
95 |
95 |
AC-4 |
15 |
15 |
30 |
30 |
55 |
55 |
AC-15 |
- |
- |
- |
- |
- |
- |
DC-13 |
- |
- |
- |
- |
- |
- |
Power P (KW) |
AC-23A |
15/10 |
30/18.5 |
30/15 |
45/22 |
37/22 |
75/37 |
AC-2 |
18.5 |
30 |
30 |
45 |
37 |
55 |
AC-3 |
11/6 |
18.5/11 |
18.5/11 |
30/13 |
22/11 |
37/18.5 |
AC-4 |
5.5/2.4 |
7.5/4 |
7.5/4 |
12/5.5 |
10/4 |
15/7.5 |
|
|
| |
|
|
| |
LW31 Combined Switch |
|
| |
.jpg) |
|
| |
Description |
LW31-20 |
LW31-32 |
LW31-50 |
W31-75 |
LW31-125 |
Rated insulation voltage Ui |
V |
440 |
690 |
690 |
690 |
690 |
Rated working voltage Ue |
V |
440 |
690 |
690 |
440 |
440 |
Rated thermal current Ith |
A |
20 |
32 |
50 |
75 |
125 |
|
|